Monitoring Power and Cooling

If the unit powers off after running for a while, check for loose power connections, power losses or surges at the power outlet, and use the show chassis command to verify that the temperature is below the shutdown threshold. If you still cannot isolate the problem, then the internal power supply may be defective. In this case, contact RUCKUS Technical Support for assistance.

The device contains temperature sensors that the software reads based on a configurable device poll time. Switch models with cooling fans have two automatic speed fan control settings based on the temperature. To protect the device from overheating, the following temperature threshold levels exist:

  • The warning level is the temperature at which the device generates a syslog message. It is configurable up to 100°C (212°F).
  • The shutdown level is the temperature at which the device reboots. It is set by the device and is not configurable. When the device temperature reaches the shutdown level, it generates a warning message that the device’s temperature is over the shutdown level and the device shuts down in two minutes. The system restarts 120 seconds after the device reaches the temperature shutdown level.

For switch models with cooling fans, the fans have two speeds, low and high. The fan speed settings are set by the device and are not configurable. During system bootup, the fans run at high speed. After bootup, the fans operate at low speed when the temperature of the switch is below the high limit temperature that is specified in the following table. If the switch reaches the high limit temperature, the fans operate at high speed until the switch reaches the low limit temperature specified in the table, at which time the fans decrease to low speed. If the switch reaches or exceeds the critical (shutdown) temperature for two minutes, the switch shuts down.

Note: In addition to the overall temperature of the device, the PoE-supported models monitor the temperature of the PoE power supply unit (PSU). When the low limit and high limit temperatures are reached, the PoE PSU fans change speed using the same algorithm as the module fans. There is no change to the Critical (shutdown) temperature value for these modules.

Temperature Thresholds

Model Low Limit Temperature High Limit Temperature Critical (Shutdown) Temperature
ICX 7150-C12P Not applicable Not applicable 109°C (228°F)
ICX 7150-C12P-ES Not applicable Not applicable 109°C (228°F)
ICX 7150-24 Not applicable Not applicable 105°C (221°F)
ICX 7150-24P

62°C (144°F)

PoE PSU: 49°C (120°F)

72°C (162°F)

PoE PSU: 57°C (135°F)

105°C (221°F)
ICX 7150-24P-ES

62°C (144°F)

PoE PSU: 49°C (120°F)

72°C (162°F)

PoE PSU: 57°C (135°F)

105°C (221°F)
ICX 7150-48 Not applicable Not applicable 105°C (221°F)
ICX 7150-48P

60°C (140°F)

PoE PSU: 49°C (120°F)

70°C(158°F)

PoE PSU: 57°C (135°F)

105°C (221°F)
ICX 7150-48P-ES

60°C (140°F)

PoE PSU: 49°C (120°F)

70°C(158°F)

PoE PSU: 57°C (135°F)

105°C (221°F)
ICX 7150-48PF

85°C (185°F)

PoE PSU: 34°C (93°F)

95°C (203°F)

PoE PSU: 41°C (106°F)

105°C (221°F)
ICX 7150-48ZP

85°C (185°F)

PoE PSU: 34°C (93°F)

95°C (203°F)

PoE PSU: 41°C (106°F)

105°C (221°F)

ICX7150-C08P

Not applicable Not applicable 108°C (226°F)

ICX7150-C10ZP

Not applicable Not applicable 104°C (219°F)

ICX7150-24F

64°C (147°F) 74°C (165°F) 85°C (185°F)

ICX7150-C08PT

-40°C (104°F) 85°C (185°F) 85°C (185°F)

To display the temperature of a device, enter the show chassis command at any level of the CLI. The show chassis command displays the current temperature, the power supply status, and temperature threshold levels. The displayed temperature reflects the temperature of the board inside the device.

device# show chassis
The stack unit 1 chassis info:

Power supply 1 (AC - PoE) present, status ok
        Model Number:   YM-1921AB06R
        Serial Number:  SA000V171708000081
        Firmware Ver:   P2H802A00
Power supply 1 Fan Air Flow Direction:  Front to Back
Power supply 2 (AC - PoE) present, status ok
        Model Number:   YM-1921AB06R
        Serial Number:  SA000V171708000083
        Firmware Ver:   P2H802A00
Power supply 2 Fan Air Flow Direction:  Front to Back

Fan 1 ok, speed (manual): 1<->[[2]]
Fan 2 ok, speed (manual): 1<->[[2]]

Fan controlled temperature: 
        Rule 1/2 (MGMT THERMAL PLANE): 60.7 deg-C
        Rule 2/2 (PoE THERMAL PLANE): 10.0 deg-C

Fan speed switching temperature thresholds:
        Rule 1/2 (MGMT THERMAL PLANE):
                Speed 1: NM<----->95       deg-C
                Speed 2:       85<----->105 deg-C (shutdown)      
        Rule 2/2 (PoE THERMAL PLANE):
                Speed 1: NM<----->41       deg-C
                Speed 2:       34<----->105 deg-C (shutdown)

Fan 1 Air Flow Direction:  Front to Back 
Fan 2 Air Flow Direction:  Front to Back 
Slot 1 Current Temperature: 61.7 deg-C (Sensor 1), 54.4 deg-C (Sensor 2), 10.0 deg-C (Sensor 3)
Slot 2 Current Temperature: NA
        Warning level.......: 102.0 deg-C
        Shutdown level......: 105.0 deg-C