Monitoring Power and Cooling
If the unit powers off after running
for a while, check for loose power connections, power losses or surges at the
power
outlet, and use the show
chassis command to verify that the temperature is below the shutdown
threshold. If you still cannot isolate the problem, then the internal power supply
may be defective. In this case, contact RUCKUS Technical Support for
assistance.
Models with Fans
The device contains temperature sensors that the software reads based on a configurable device poll time. The device has two automatic speed fan control settings based on the temperature. To protect the device from overheating, the following temperature threshold levels exist:
- The warning level is the temperature at which the device generates a syslog message.
- The shutdown level is the temperature at which the device reboots. It is set by the device and is not configurable. When the device temperature reaches the shutdown level, it generates a warning message that the device’s temperature is over the shutdown level and the device shuts down in two minutes. The system restarts 120 seconds after the device falls back to the temperature shutdown level.
The switch fans have two speeds, low and high. The fan speed settings are set by the device, and are not configurable. During system bootup, the fans run at high speed. After bootup, the fans operate at low speed when the temperature of the switch is below the high limit temperature that is specified in the following table. If the switch reaches the high limit temperature, the fans operate at high speed until the switch reaches the low limit temperature specified in the table, at which time the fans decrease to low speed. If the switch reaches or exceeds the critical (shutdown) temperature for two minutes, the switch shuts down.
Temperature Thresholds
| Switch Model | Low Limit Temperature (°C) | High Limit Temperature (°C) | Critical (Shutdown) Temperature (°C) |
|---|---|---|---|
| ICX8100-C08PF | 37 | 45 | 64 |
| ICX8100-C08PF-V | 37 | 45 | 64 |
| ICX8100-C16P | 37 | 45 | 64 |
| ICX8100-24 | 37 | 45 | 64 |
| ICX8100-24P | 40 | 48 | 65 |
| ICX8100-24P-V | 40 | 48 | 65 |
| ICX8100-48 | 40 | 48 | 65 |
| ICX8100-48P | 40 | 48 | 65 |
| ICX8100-48PF | 40 | 48 | 65 |
| ICX8100-48PF-V | 40 | 48 | 65 |
To display the temperature of a
device, enter the show
chassis command at any level of the CLI. The show chassis command
displays the current temperature, the power supply status, and temperature threshold
levels. The displayed temperature reflects the temperature of the board inside
the
device.
device# show chassis The stack unit 1 chassis info: Power supply 1 (AC - PoE) present, status ok Fanless model Slot 1 Current Temperature: 44.7 deg-C (Sensor 1), 46.2 deg-C (Sensor 2), 45.7 deg-C (Sensor 3), 52.0 deg-C (Sensor 4), 45.0 deg-C (Sensor 5) Warning level.......: 77.0 deg-C Shutdown level......: 80.0 deg-C Boot Prom MAC : 5c83.6c3f.d5ea Management MAC: 5c83.6c3f.d5ea Stack unit-1: The system was last powercycled on Friday, 2024-11-08 at 17:23:28+0000 (UTC), powercycle count: 16